ELEC 226, Spring 2012
Prof. Rich Kozick
Laboratory 4: Transformers
Objective: We will make measurements with the transformers and
compare results with the equations for the linear
transformer in Figure 13-8 and Section 13-2.2, and also the ideal transformer in Section 13-4. Notes
are provided that summarize the formulas for linear
and ideal transformers as well as the conditions
required for ideal transformer approximation.
Please keep your circuits assembled until you discuss the results with
the instructor, and bring your results to class on March 29.
Lab Activities:
- Please study the analysis of
the linear transformer and make sure you understand equations
(13.23)-(13.25) and the notes.
- We will use the outer
terminals on the transformer box as the primary and the AC cord terminals
as the secondary, so the turns ratio is expected to be approximately n = N2 / N1
= 10 (as defined in equations 13.35 and 13.36). Apply a 1 volt sinusoidal
voltage source at 200 Hz to the primary side of your transformer. Make
measurements at the secondary terminals to determine the turns ratio (n)
and the “dots” on the primary and secondary sides of your
transformer. Do a quick check to see if n remains the same if you change the frequency. Also, apply a
10 V sinusoid at 200 Hz to the secondary, and measure the voltage at the
primary. See if the ratio is close to 1/n.
- Use a frequency of 200 Hz and
characterize your transformer at this frequency. That is, estimate the
internal resistances of the primary and secondary coils (R1
and R2) and the self-inductances (L1
and L2). In addition, devise a procedure to estimate the
mutual inductance, M, and the
coefficient of coupling, k (defined via ).
You should use a larger input voltage when applying the source to the AC
cord terminals.
Discuss your planned procedure with
the instructor before making measurements.
- Examine your results and
consider how well your transformer satisfies the conditions
required for ideal transformer approximation.
- Next add a load resistor of
about RL = 5,000 ohms
across the secondary terminals, so current will flow in both the primary
and the secondary. Measure the voltage phasors VT, V1, V2, and use these to
calculate the current phasors I1 and I2
(use a 10 ohm helper resistor). Compare the measured results with the
linear transformer equations as well as the ideal transformer equations,
which are as follows:
Determine how closely your measured results match with the linear and
ideal transformer equations. In particular, calculate the “reflected
impedance” of the load using the linear and ideal transformer
models, and see which one agrees with your measured results.
- Repeat step 5 at 20 kHz
instead of 200 Hz. Are the results closer to the ideal transformer model?
Each lab group should prepare a summary of your analysis and
measured results and discuss it with the instructor before leaving. Then each
student is asked to explain all analysis and measurements for submission in
class on Tuesday, April 3, 2012.
In the work that you submit, you should include for each
case (1) a diagram of the circuit that you constructed, showing the component
values and the voltages and currents; (2) your measured values of voltage
and/or current; and (3) the computations that you performed. Your work will be
evaluated based on the correctness of the approach rather than the degree of
agreement between measurement and analysis. (The real transformers contain some
features that are not modeled by the analysis.)